M-NCPPC Park Police and ITC Headquarters Roof Structure Evaluation and Joist Reinforcement
Roof and window leak investigation, evaluation of the existing steel joist roof structure, and joist and joist girder reinforcement design for a four-story headquarters building in Landover, Maryland.

Overview
The Maryland-National Capital Park and Planning Commission Park Police and ITC Headquarters is a four-story steel-framed building in Landover, Maryland, built in 1983. During interior renovations in 2021, REI investigated leaks at the roof and fourth-floor windows with test cuts, moisture readings and water testing, and recommended repairs. In 2022, before the roof was recovered, REI was asked to confirm that the existing roof structure could carry the new roofing. REI measured the steel joist girders and the 14-inch joists spanning 25 feet between them. The analysis showed the joists were significantly undersized for the current county snow load even under the existing roof. The deficiency was worse in the snow drift zones created by the rooftop screen walls and large rooftop units. REI recommended raising or removing the screen walls to reduce drifting and designed reinforcement for the light joists, the heavily loaded joists at the rooftop units and the joist girders. REI developed alternative reinforcement schemes so the contractor and owner could compare costs, and revised the weld details during construction.
Scope of Work
2021: investigated roof and fourth-floor window leaks with test cuts, moisture readings and water testing, and recommended repairs
2022: field-measured the existing joist girders, joists, bridging and connections and identified the original joist series
Calculated balanced snow, drift, dead and equipment loads, including drifts at the rooftop screen walls and large rooftop units
Analyzed the joists and joist girders and found them inadequate for current code snow loads
Recommended raising or removing the screen walls to reduce drift loads
Designed reinforcement of the light joists, the heavily loaded joists at the rooftop units and the joist girders, with alternative schemes for pricing
Revised the reinforcement weld details during construction
Project Details
Client: Maryland-National Capital Park and Planning Commission
Location: Landover, Maryland
Market: Government
Project Category: Structural Repair
REI Role: Structural Engineer
Roof and window investigation: 2021
Roof structure evaluation and reinforcement design: 2022
Building: Four-story steel-framed office building built in 1983
System(s): Steel joist girders and 14-inch open-web steel joists on a 25-foot column grid; welded bar and angle reinforcement
Services: Leak Investigation • Structural Evaluation • Snow and Drift Load Analysis • Joist Reinforcement Design