Fort Meade Building K Roof Wind Uplift Analysis

Wind uplift analysis and insulation and cover board attachment requirements for new membrane roofs at the stair towers and main entrance of a building at Fort Meade, Maryland.

Fort Meade Building K Roof Wind Uplift Analysis

Overview

REI was retained by the roofing contractor to analyze wind uplift for the new fully adhered PVC membrane roofs at the three stair towers and the main entrance of Building K at Fort Meade, Maryland. REI calculated components and cladding pressures under ASCE 7-10 and found maximum uplift pressures of 75 psf at the stair towers and 63 psf at the main entrance. REI prepared a roof zone drawing showing the field, perimeter and corner zones on each roof. Using the manufacturer's attachment tables, REI then set the number and layout of fasteners per cover board in each zone, along with the fastener type and minimum penetration through the steel deck. REI delivered stamped calculations and the roof zone drawing so the roofing met code and the manufacturer's requirements.


Scope of Work

  • Reviewed the architectural roof plans and the specified roofing assembly

  • Calculated components and cladding wind uplift pressures under ASCE 7-10 for the stair tower and main entrance roofs

  • Prepared a roof zone drawing identifying field, perimeter and corner zones

  • Set the number and layout of cover board fasteners per board in each zone, and fastener type and deck penetration

  • Issued stamped calculations and a summary letter


Project Details

Client: U.S. Army, Fort George G. Meade

Location: Fort Meade, Maryland

Market: Government

Project Category: Roofing

REI Role: Wind Uplift and Ballast Design Engineer

Analysis: 2019

Building: Multi-story building with stair tower and entrance roofs

System(s): Fully adhered PVC membrane over mechanically fastened cover board on steel deck

Services: Wind Uplift Analysis • Roof Attachment Design